Glass insulator——DOUBLE UMBRELLA U70BP

OUR PRODUCTS

Recognized globally, we hold prestigious international certifications including ISO, CE, KEMA, and CESI, ensuring uncompromising quality and reliability worldwide.

GLASS INSULATOR DOUBLE UMBRELLA U70BP

The KZAN U70BP is a 70 kN double-umbrella (anti-pollution) cap-and-pin toughened glass suspension insulator built to IEC 60305. With a nominal structure height of 146 mm, an enlarged nominal diameter of 280 mm, and an extended creepage distance of 450 mm, its dual-shed profile is engineered for medium to heavy pollution areas where standard insulators would accumulate contamination. The U70BP offers the same visible self-breakage and standard ball-and-socket interchangeability as the U70B, while its longer creepage path raises the pollution flashover withstand for 110 kV to 220 kV transmission lines.

Phone 86-19886663636
Whatsapp 86-19886663636

Details & Specifications

With stable chemical properties and anti-aging characteristics, glass insulators ensure safe power transmission, reduce operational risks, and provide long-term, reliable service for power infrastructure.

Key Features

  • Double-umbrella (anti-pollution) profile with 450 mm creepage for heavy-pollution service.
  • High mechanical strength (70 kN failing load) and thermal stability.
  • Excellent dielectric properties and anti-aging characteristics.
  • Visible self-breakage enables fast on-site fault detection without system outage.

Technical Specifications

Project Parameter Values
PRODUCT MODELDOUBLE UMBRELLA U70BP/146D
Nominal Diameter D (mm)280
Nominal Structure Height H (mm)146
Nominal Creepage Distance (mm)450
Socket Coupling Size (mm)16
Mechanical Failing Load (kN)70
Mechanical Routine Test Load (kN)35
Wet Power Frequency Withstand Voltage (kV)45
Dry Lightning Impulse Withstand Voltage (kV)110
Impulse Puncture Voltage (kV)2.8
Power Frequency Puncture Voltage (kV)130
Radio Interference Voltage (μV)≤ 50
Visible Corona Voltage (kV)18 / 22
Power Frequency Arc Test (s/kA)0.12s / 20kA

Applications

  • 110 kV–220 kV AC overhead transmission lines in medium to heavy pollution areas (coastal, industrial, desert)
  • Substation busbar and tension string installations exposed to contamination
  • Railway electrification and other overhead networks in polluted environments
  • Retrofit of standard insulators where pollution flashover risk is high

Standards & Compliance

All KZAN U70BP insulators are manufactured and tested in accordance with IEC 60305 and IEC 61109, and verified by third-party laboratories including KEMA and CESI. Routine and type tests cover mechanical failing load, electrical withstand voltage, and puncture performance to ensure reliable field operation.

Frequently Asked Questions

What does the 'P' in U70BP mean?

In IEC nomenclature, 'U' is a cap-and-pin suspension insulator, '70' is the 70 kN nominal mechanical failing load, 'B' is the ball-and-socket coupling, and 'P' denotes an anti-pollution (pollution-resistant) double-umbrella design. The U70BP is therefore a 70 kN anti-pollution double-umbrella glass suspension insulator.

What is the difference between U70B and U70BP?

The U70BP shares the same 70 kN load, 146 mm structure height and ball-and-socket fittings as the standard U70B, but uses a double-umbrella profile with an extended 450 mm creepage distance (versus 320 mm on the standard U70B) for service in polluted environments.

Which pollution levels is the U70BP suitable for?

It is engineered for medium to heavy pollution areas — coastal regions, industrial zones, and desert or railway corridors — where its longer creepage path raises the pollution flashover withstand voltage.

Can U70BP replace standard U70B strings?

Yes. With the same ball-and-socket fittings and 146 mm structure height, the U70BP is fully interchangeable with standard U70B strings in both new-build and retrofit projects.

What standards and certifications apply?

Manufactured and tested to IEC 60305 and IEC 61109, with routine and type tests verified by third-party laboratories including KEMA and CESI. The plant also holds ISO 9001, CE and other international certifications.